LMW3 ACB 1600 Amp Air Circuit Breaker AC 400V/690V

Rated current:200、400、630、800、1000、1250、1600A
Rated working voltage: AC400V、AC690V  50Hz
Rated insulation voltage: AC1000V
Installation method: drawer type, fixed type
Wiring method: horizontal wiring
Operation mode: electric operation, manual operation
Tripping type: intelligent controller, under-voltage tripper, shunt release tripper
Usage Category: Class B
Pollution level:3
Standard: IEC 60947-2

LMW3 Series Air breaker circuit manual

The LMW3 series universal circuit breaker (hereinafter referred to as the circuit breaker) is suitable for power distribution networks with AC 50Hz, rated voltage up to 690V and below, and rated current 200A~1600A. It is used to distribute electric energy and protect lines and power equipment from overload, under-voltage, short circuit, single-phase grounding and other faults. The circuit breaker has intelligent protection function and precise selective protection, which can improve the reliability of power supply and avoid unnecessary power outages. At the same time, it has an open communication interface and can perform “four remotes” to meet the requirements of the control center and automation system.

Product Parameters

Rated current 200、400、630、800、1000、1250、1600
Rated limit short-circuit breaking capacity Icu(kA) 400V 65
690V 50
Rated operating short-circuit breaking capacity Ics(kA)

400V 55
690V 42
Rated short-time withstand current Icw(kA)/1s

400V 50
690V 42
Rated operating voltage Ue(V) AC400,AC690
Rated insulation voltage Ui(V) AC1000
Rated impulse withstand voltage Uimp(V) 12000
Power frequency withstand voltage U 220V 1min 50Hz