LMM1E Electronic adjustable type MCCB Molded Case Circuit Breaker

Standard: IEC60947-2
Model: LMM1E
Poles: 3P,4P
Frame size: 160,250,400,630,800,1250,1600
Rated operational voltage: 400/415/690V
Rated insulation voltage: 1000V
Trip unit type: electronic type
Breaking capacity code: L,M,H
Installation method: Fixed type; plug-in type
Adjustable Tripping Setting: Ir, Isd, Ii, tR, tsd, Ip
Ambient Temperature: -25…+40 ºC
Certificate: CE, CB
Available in black or white covers

LMM1 MCCB Manual

LMM1E series MCCB with electronic trip unit providing LSI protection. This molded case circuit breaker is suitable for applications with AC 50Hz, rated voltage 690V and below, and rated current up to 1600A.
Compared with thermal-magnetic trip units, electronic trip units can be more accurately set in terms of trip time and current threshold, thereby better protecting the safety of equipment in the circuit.
  • IR: Overload long delay setting current
  • Isd: Short-circuit short delay setting current
  • Ii: Short-circuit instantaneous setting current
  • tR: Overload long delay setting time
  • tsd: Short-circuit short delay setting time
  • Ip: Overload pre-alarm setting current
Frame size Inm(A) 160 250
Rated operational current In(A) 32,63,100,125,160 160,250
Tripper rated current Ir(A) 63,75,80,90,100,125,140,150,160 100,125,140,150,160,180,200,225,250
Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 400/690
Breaking capacity code S H S H
Number of poles 3P, 4P
Rated service short circuit breaking capacity Ics (kA) 400/415V 18 25 18 25
Rated ultimate short circuit breaking capacity Icu (kA) 25 35 25 35
Utilization category A B
Trip unit type
Electronic
Mechanical life (times) 8500
Electrical life (times) 1500

 

Frame size Inm(A) 400 630 800
Rated operational current In(A) 400 500,630 630,800
Tripper rated current Ir(A) 160,180,200,220,

240,280,320,360,400

250,280,315,350,380,

440,500.570,630

320,400,450,500,550,

630,700,750,800

Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 400/690
Breaking capacity code H H H
Number of poles 3P, 4P
Rated service short circuit breaking capacity Ics (kA) 400/415V 35 35 50
Rated ultimate short circuit breaking capacity Icu (kA) 50 50 65
Utilization category B B B
Trip unit type
Electronic
Mechanical life (times) 4000 4000 2500
Electrical life (times) 1000 1000 500

 

Frame size Inm(A) 1250 1600
Rated operational current In(A) 630,800,1000,1250 800,1000,1250,1600
Tripper rated current Ir(A) 500,800,700,800,900,1000,1100,1200,1250 630,800,900,1100,1250,1400,1500,1600
Rated insulation voltage Ui(V) 1000
Rated impulse withstand voltage Uimp(kV) 8
Rated operational voltage Ue(V) 400/690
Breaking capacity code H H
Number of poles 3P, 4P
Rated service short circuit breaking capacity Ics (kA) 400/415V 50 50
Rated ultimate short circuit breaking capacity Icu (kA) 65 85
Utilization category B B
Trip unit type
Electronic
Mechanical life (times) 2500 2500
Electrical life (times) 500 500