Model Definition
Main Technical Parameters
Frame size | 100 | 160 | 250 | 630 | 1600 | 3200 | |
Rated operating current le (A) | 16,20,25,32, 40,50,63,80,100 |
125,160 | 200,225,250 | 315,350,400, 500,630 |
800,1000 1250,1600 |
2000,2500 3200 |
|
Rated insulation voltage | 690V | 800V | |||||
Rated impulse withstand voltage | 8KV | 12KV | |||||
Rated working voltage | AC400V/50Hz | ||||||
Use category | AC-33iB | ||||||
Rated short circuit making capacity | 8KA | 17KA | 26KA | 67.5KA | |||
Rated short time withstand current | 5kA/30ms | 10kA/60ms | 12.6kA/60ms | 32kA/60ms | |||
Switching time | 2.5s | 1.2s/2.5s | 1.2s | 1.8s | 2.4s | ||
Rated short circuit pulse current | Frount fuse 50KA | Front fuse 90KA | |||||
Note. 630 frame productiont operation time is divided into 1.2s (series motor), 2.5s (synchronous motor) |
Switch Structure Description
(1) Electrical key lock: electrical key lock control circuit power, open, the switch to achieve automatic and remote operation, closed, the switch can only be manuallyoperated.
(2) Operating handle: the electrical lock must be closed when operating the switch with operating handle.
(3) Mechanical padlock: when maintenance, first use the operating handle to make the switch in the state of “O off” state, then pull up the mechanical hang.
(4) Position indication: mark the working position of the switch (l common use, O power off, ll standby).
Y-700 type Y-701 type Y-702 type Y-703 type
</p>(LED controller) (LED indicator light controller) (LCD controller) (LCD controller)
Product model | Y-701 | Y-702 | Y-703 |
Installation | Split type | ||
Display mode | indicator light | LCD | LCD |
Self-throw self-restore | ● | ● | ● |
Self-throw non self-restore or complementary | ● | ● | ● |
Route ll priority | ● | ● | ● |
Motor start function | ● | ● | ● |
Common power detection | Four-phase detection,three-phase voltage over-voltage detection | ||
Standby power detection | Four-phase detection,three-phase voltage over-voltage detection | ||
Passive fire input | ● | ● | ● |
DC9-36V Active fire input DC9-36V | ● | ● | ● |
Conversion delay adjustable | ● | ● | ● |
Voltage real-time display | ○ | ● | ● |
Common and standby electrical indication | ● | ● | ● |
Common and standby overvoltage and undervoltage adjustable | ○ | ● | ● |
Generator start and stop time adjustable | ○ | ●(F/F1) | ●(F/F1) |
Programmable outlet | ○ | ● | ● |
RS485 communication function | ○ | ●(Optional) | ●(Optional) |
Frequency monitoring | ○ | ○ | ● |
Phase sequence detection | ○ | ○ | ● |